183 Water Street • New Haven, CT 06511 • Phone (203) 776-0473 • FAX (203) 773-1019 • www.hydrolevel.comMODEL 3200Temp Limit / LWCO Controlwith Thermal
2MOUNTING THE CONTROLSTEP 1Two mounting positionsare available on the back of the control(Fig. 1). Select which of the two positions(2 knockouts) is b
WIRINGSTEP 1 Connect 120 VAC Hot toterminal L1. Connect 120 VAC Neutralto terminal L2. Disconnect means andoverload protection as required (pro-vided
NOTE: Settings can be checked using the TEST/SETTINGSButton. See page 5 for details.Setting the High Limit The high limit is factory set at 190°F. To
5TROUBLESHOOTINGBurner Will Not Fire See Flow Chart 1, page 6Burner Will Not Shut Down See Flow Chart 2, page 7Temperature Display ExceedsHigh Limit S
6NOYES NOIs theThermostat (T-T) Calling for Heat?Is There24 VACBetween B1and B2?NOIs the Domestic Water (I1-I2) Calling forHeat?NOIs theLow Limit Dial
7YESRecheckWiring.ReplaceControl.When there is no call to fire the burner, the voltageshould be 0 volts between B1 and B2. Make sure the burner is wi
883 Water Street • New Haven, CT 06511 • Phone (203) 776-0473 • FAX (203) 773-1019 • www.hydrolevel.comREMOTE MOUNTING KITSMAINTENANCERemove the Elect